Numerical analysis of heat and mass transfer for water recovery in an evaporative cooling tower
- 주제(키워드) Condensation , Cooling tower , Heat exchanger , Mass transfer , Water recovery
- 발행기관 서강대학교 일반대학원
- 지도교수 손기헌
- 발행년도 2018
- 학위수여년월 2018. 2
- 학위명 석사
- 학과 및 전공 일반대학원 기계공학과
- 실제URI http://www.dcollection.net/handler/sogang/000000062904
- 본문언어 영어
- 저작권 서강대학교 논문은 저작권보호를 받습니다.
초록/요약
Numerical analysis is performed on a condensing heat exchanger, which consists of humid air channels and cold ambient air channels, for water recovery in an evaporative cooling tower. The humid air including water vapor produced in an evaporative cooling tower is cooled by the ambient air so that the water vapor is condensed and recovered to the liquid water. The conservation equations of mass, momentum, energy and vapor concentration in each fluid region and the energy equation in a solid region are simultaneously solved with the heat and mass transfer boundary conditions coupled to the effect of condensation on the channel surface. Computations are carried out to predict the water recovery rates in parallel, counter and cross-flow type heat exchanger.